FZW28(VSP5)-12 Outdoor boundaries vacuum load switch
Apply to rated voltage 12KV. Rated frequency 50HZ outdoor AC distribution equipment , use for opening .closing load current and closing short circuit current . Applicable to substations and industrial and mining enterprises and city, rural network for protection and control purposes, and city, rural network automatic distribution net and frequent operation place .
Applicable to operation of control switch of overhead line distribution systems, there are several types, VPS-12-type boundaries vacuum load switch with no oil, institutional simple. Reliable, no maintenance and other advantages, has been widely used. The product with the FDR-based fault detector or RTU remote terminal unit equipment combine to form a very simple structure, distribution automation system that allows the automatic overhead lines fault location and fault segment of the automatic quarantine. In order to update our existing distribution switchgear, so free of oil and automation features of the distribution equipment for the transformation.
The use of environmental conditions:
1. Altitude: ≤2000m.
2. Air temperature: -40℃ ~ +85℃
3. Relative humidity: month average≤90%,day average ≤95%
4. earthquake intensity: ≤8 class
5. pollution withstand:III class
6.icing thickness:10mm
7.wind pressure: ≤700Pa(=wind speed 34m/s).
Mainly technical parameters
Item | Units | Technical Parameters |
rated voltage | kV | 12 |
rated current | A | 630 |
rated frequency | Hz | 50 |
rated short time withstand current\time | kA | 20,4S |
rated short-circuit closing current (peak) | kA | 50 |
operate voltage | V | AC220(80%-110%) |
1min power frequency voltages | Earth | kV | 50(GB42) |
Inter-phase | 50(GB42) |
Fracture | 50(GB48) |
Lightning impulse withstand voltage | Earth | kV | 95(GB75) |
Inter-phase | 95(GB75) |
Fracture | 110(GB84) |
insulation resistance | Earth | MΩ | 2000 |
Inter-phase | 2000 |
Fracture | 2000 |
per phase lead circuit resistance | µΩ | ≤500 |
rated current disconnection life | Times | 10000 |
mechanical life | Times | 30000 |
weight | kg | 185 |
Contact closing bounce duration | ms | ≤5 |
Three phase closing and opening non-synchronism | ms | ≤2 |
closing time | ms | 120-180 |
opening time | ms | 500-900 |
contact travel | mm | 8-9 |
contact over travel | mm | 2.5-4 |
isolation fracture distance | mm | 25-30 |
isolation fracture over-distance | mm | 7-14 |
SF6 year leakage | | <1% |
SF6 gas water contents | PPm | <2 |
reference standards | | IEC265-1 |